| Notes |
| Date |
Text |
| 2001-04-03 00:00:00 | *******************DENIED*************** | | | | | | | | | MECHANICAL PERMIT REQUIRED. PLANS NEED | | | TO INDICATE CONDENSATE DRAIN LINE. | | | ALSO AN AUXILIARY DRAIN PAN WITH | | | OVERFLOW PROTECTION REQUIRED AS PER | | | 1997 SMC 304.8.6. | | | | | | NOTE 5 ON THE AIR CONDITIONING | | | SPECIFICATION, INDICATES 105 CFM MAKE | | | UP VENTALATION AIR,PLANS NEED TO | | | REFLECT LOCATION OF MAKE UP AIR.SHOW | | | O.A. CALCULATION AS PER ASHRAE 62-89. |
|