| Plan Review Notes For Permit 01020521 |
| Permit Number |
01020521 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-06 00:00:00 | ******************** UNSAT ************ | | | | | | 1)NOTE:PLANS NEED TO HAVE BRANCH | | | CIRCUIT#`S NEED TO BE SHOWN ON PLANS | | | ANDSUBMIT PANEL SCHEDULE THAT | | | CORRELATESWITH #`S ON PLANS. | | | | | | 2)NOTE: PLANS SHOW NEW ADDED LOAD. WHAT | | | ABOUT EXSITING LOAD? | | | ALSO PLANS SHOW ADDING CIRCUITS TO | | | PANELIN ADJACENT SPACE. THIS IS NOT | | | PERMITTED | | | | | | 3) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT8372 |
|