Plan Review Notes
Plan Review Notes For Permit 01020521
Permit Number 01020521
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-06 00:00:00******************** UNSAT ************
  
 1)NOTE:PLANS NEED TO HAVE BRANCH
 CIRCUIT#`S NEED TO BE SHOWN ON PLANS
 ANDSUBMIT PANEL SCHEDULE THAT
 CORRELATESWITH #`S ON PLANS.
  
 2)NOTE: PLANS SHOW NEW ADDED LOAD. WHAT
 ABOUT EXSITING LOAD?
 ALSO PLANS SHOW ADDING CIRCUITS TO
 PANELIN ADJACENT SPACE. THIS IS NOT
 PERMITTED
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372