| Plan Review Notes For Permit 01020495 |
| Permit Number |
01020495 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-03-22 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT PER F.A.C. | | | F.S. 471.025 / 481.221 ALL CHANGES ON | | | SIGNED AND SEALED DOCUMENTS ARE TO BE | | | SIGNED/INITIALED AND DATED BY THE ARCH/ | | | ENGINEER OF RECORD. | | | | | | 2)NOTE: PLEASE PROVIDE INFORMATION FOR | | | NEW RISER DIAGRAM SUBMITTED. NO WIRE | | | SIZES,CONDUIT SIZES FOR DISCONNECTS, | | | PANELS. | | | | | | 3)NOTE: PLEASENOTE 373-8 FOR | | | DISC/PANELS BEING USED AS RACEWAYS.FEED | | | FOR 100A DISCONNECT IS SHOWN GOING | | | THROUGH, 150A. | | | | | | 4)NOTE: PLEASE SHOW WHERE NEW SERVICE | | | ISGOING TO BE. HOUSE/OR COTTAGE. | | | CONDUIT SIZES UNDERGROUND.ETC | | | IF SERVICE FOR COTTAGE IS COMING FROM | | | MAIN HOUSE THEN LOAD CALCULATIONS OF | | | EXSITING NEEDS TO BE SUBMITTED AND | | | INCLUDE NEW COTTAGE LOAD. | | | | | | 5)NOTE: PLEASE NOTE, STILL NEED THE AIC | | | RATINGS OF ANY NEW EQUIPMENT. PER 110-9 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, OR | | | IF I CAN BE OF ANY ASSISTANCE. PLEASE | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|