Plan Review Notes
Plan Review Notes For Permit 01020495
Permit Number 01020495
Review Stop E
Sequence Number 1
Notes
Date Text
2001-02-16 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT A REVISED RISER
 DIAGRAM. SEPARATE METER FOR GUEST
 COTTAG IS NOT PERMITTED.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IFTHERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372