| Plan Review Notes For Permit 01020445 |
| Permit Number |
01020445 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-13 00:00:00 | 1) HVAC DUCT SMOKE DETECTORS WHEN | | | ACTIVATED SHALL CAUSE AIR HANDLING | | | EQUIPMENT TO SHUT DOWN AND CAUSE THE | | | FIRE ALARM SYSTEM TO ACTIVATE. | | | 2) FIRE ALARM SYSTEM TO BE CLASS A OR | | | FULLY ADDRESSABLE. | | | 3) WHEN ACTIVATED, THE FIRE ALARM | | | SYSTEM IS TO BE AUDIBLE THROUGHOUT. | | | 4) ACTIVATION OF ANY FIRE ALARM | | | EQUIPMENT ON THE 20TH FLOOR SHALL | | | CAUSE THE STAIRWAY FANS TO ACTIVATE. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|