| 2001-02-13 00:00:00 | 1) PLEASE INDICATE THE INSTRUCTIONS |
| | THAT WILL BE GIVEN FOR THE TAPED |
| | MESSAGE PORTION OF THE FIRE ALARM |
| | SYSTEM. |
| | 2) THE FIRE ALARM SYSTEM AND FIRE |
| | SPRINKLER SYSTEM TO BE MONITORED BY |
| | A LICENSED UL LISTED CENTRAL STATION |
| | APPROVED BY THE FIRE RESCUE DEPARTMENT. |
| | 3) HOW IS THE INSTALLATION OF THE NEW |
| | FIRE ALARM SYSTEM GOING TO BE PERFORMED |
| | AND HOW LONG WILL THE EXISTING FIRE |
| | ALARM SYSTEM BE INSERVICE. WILL ANY |
| | GAPS IN COVERAGE OCCUR. |
| | 4) SMOKE DETECTORS MUST BE INSTALLED A |
| | MINIMUM OF THREE FEET FROM AIR |
| | CONDITONING DIFFUSERS. |
| | 5) THE NEW ATRIUM FIRE ALARM EQUIPMENT |
| | MUST BE IDENTIFIED AS HOW IT EFFECTS THE |
| | OPERATION OF THE REQUIRED SMOKE CONTROL/ |
| | EXHAUST FEATURES OF THE ATRIUM PORTION |
| | OF THE BUILDING. |
| | 6) PLEASE INDICATE SEQUENCE OPERATIONS |
| | FOR THE STAIRWAY FANS. |
| | 7) LOCKS ON EXIT DOORS THAT ARE |
| | INTERFACED WITH THE FIRE ALARM SYSTEM |
| | ARE TO MEET SPECIAL LOCKING ARRANGEMENTS |
| | PER THE LIFE SAFETY CODE. |
| | 8) THE DUCT SMOKE DETECTORS WHEN |
| | ACTIVATED ARE TO SHUT DOWN ALL AIR |
| | HANDLING EQUIPMENT AND ACTIVATE THE |
| | FIRE ALARM SYSTEM. |
| | 9) WILL THE FIRE ALARM SYSTEM WHEN |
| | ACTIVATED, ALERT THE FLOOR OF INCIDENT, |
| | THE FLOOR ABOVE AND BELOW OR THE WHOLE |
| | BUILDING. |
| | 10) ARE ALL HOOD EXTINGUISHING SYSTEMS |
| | AT THE COMPLEX TIED INTO THE FIRE |
| | ALARM SYSTEM. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |