2001-06-09 00:00:00PLUMBING PLAN REVIEW"DENIED"
 (1) PROVISO DATED 5-6-01 WITHDRAWN DUE
 TO REVISION DATED 5-23 01,UNSAT.
 (2) PLUMBING REVISION,TO BE SIGNED AND
 SEALED BY ENGINEER OF RECORD.
 THIS DESIGN IS TO COMPLY WITH STD PLBG.
 CODE 94,SEC 921,HORZONTAL WASTE & VENT
 SYSTEM.MOP SINK CAN NOT BE DELETED WITH-
 OUT DEPT OF HOTEL BUSINESS REGULATION
 APPROVAL.
 (3) GAS DRAWGING NOT APPROVED,SEE GAS
 PERMIT APPLICATION REQUIRMENTS, ANSWER
 EA ITEM CIRCLED, SHOW LOCATION OF EMERG-
 ENCY GAS SOLENOID, FOR HOOD SHUT DOWN,
 THIS IS TO BE BELOW CEILING, WITH MANUAL
 SOV UP STREAM OF SOLENOID VALVE, WITH A
 UNION DOWN STREAM. SGC 97 SEC 403.
 DRWG TO BE SIGNED & SEALED BY ENGINEER
 OF RECORD. SEPERATE PERMIT IS REQUIRED.
 END OF COMMENTSPAUL SCHMITZ