| Plan Review Notes For Permit 01020317 |
| Permit Number |
01020317 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-06-09 00:00:00 | PLUMBING PLAN REVIEW"DENIED" | | | (1) PROVISO DATED 5-6-01 WITHDRAWN DUE | | | TO REVISION DATED 5-23 01,UNSAT. | | | (2) PLUMBING REVISION,TO BE SIGNED AND | | | SEALED BY ENGINEER OF RECORD. | | | THIS DESIGN IS TO COMPLY WITH STD PLBG. | | | CODE 94,SEC 921,HORZONTAL WASTE & VENT | | | SYSTEM.MOP SINK CAN NOT BE DELETED WITH- | | | OUT DEPT OF HOTEL BUSINESS REGULATION | | | APPROVAL. | | | (3) GAS DRAWGING NOT APPROVED,SEE GAS | | | PERMIT APPLICATION REQUIRMENTS, ANSWER | | | EA ITEM CIRCLED, SHOW LOCATION OF EMERG- | | | ENCY GAS SOLENOID, FOR HOOD SHUT DOWN, | | | THIS IS TO BE BELOW CEILING, WITH MANUAL | | | SOV UP STREAM OF SOLENOID VALVE, WITH A | | | UNION DOWN STREAM. SGC 97 SEC 403. | | | DRWG TO BE SIGNED & SEALED BY ENGINEER | | | OF RECORD. SEPERATE PERMIT IS REQUIRED. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|