Plan Review Notes
Plan Review Notes For Permit 01020317
Permit Number 01020317
Review Stop E
Sequence Number 1
Notes
Date Text
2001-03-06 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS AND CORRELATE WITH A
 SUBMITTED PANEL SCHEDULE.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER 220 AND INCLUDE ALL KITCHEN
 EQUIPMENT ETC. PLEASE NOTE ALL
 CONTINUOUS ARE AT 125%.
  
 3)NOTE: PLEASE PROVIDE CLARIFICATION ON
 MAIN DISCONNECT? PANEL SHOWN AS MLO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVEIEW.