| 2001-03-06 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANS AND CORRELATE WITH A | | | SUBMITTED PANEL SCHEDULE. | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | PER 220 AND INCLUDE ALL KITCHEN | | | EQUIPMENT ETC. PLEASE NOTE ALL | | | CONTINUOUS ARE AT 125%. | | | | | | 3)NOTE: PLEASE PROVIDE CLARIFICATION ON | | | MAIN DISCONNECT? PANEL SHOWN AS MLO. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVEIEW. | | | 561-659-8096 EXT 8372 |
|