| Plan Review Notes For Permit 01020317 |
| Permit Number |
01020317 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-07 00:00:00 | PERMIT # 01020317 | | | 446 NORTHWOOD RD | | | HATCHEY CONSTRUCTION | | | 588-8288 | | | | | | 1)- FL HANDICAPPED CODE 4.1.6.2.2(3)A: | | | SHOW RAMP AT FRONT ENTRY OF BUILDING. | | | HANDICAPPED RAMP SLOPE MAY BE BETWEEN | | | 1:10 & 1:12 IS ALLOWED FOR A MAXIMUM | | | RISE OF 6 INCHES. | | | | | | (2)- FL HANDICAPPED CODE 4.16: | | | THE FLOOR PLAN AND THE HANDICAPPED | | | TOLIET DETAILHAVE DISCREPANCIES IN | | | SIZE AND LAY OUT. | | | | | | (3)- NOTE 5&6 SHOW THE REPLACEMENT OF | | | WINDOWS WHICH WILL REQUIRE A ACCEPTANCE | | | REPORT, EITHER SBCCI OR DADE COUNTY | | | PRODUCT APPROVAL (2 COPIES). | | | | | | (4)- NOTE #14: SBC 1204.2 WALLS & FLOORS | | | OF ALL PUBLIC RESTROOMS SHALL BE LINED | | | WITH NONABSORBANT MATERIAL TO A HEIGTH | | | OF 4 FT. ABOVE THE FLOOR. | | | | | | (5)- THE STOREFRONT DOOR AND WINDOWS | | | ARE TO BE UNDER SEPERATE PERMIT AND | | | FEES. 2 COPIES OF AN PRODUCT ACCEPTANCE | | | REPORT WILL BE REQUIRED. S.B.C.C.I. | | | REPORT OR DADE COUNTY WILL BE ACCEPTABLE | | | IF THE REPORT HASN,T HAD LARGE MISSLE | | | IMPACT TESTING STORM SHUTTERS WILL BE RE | | | QUIRED THAT HAVE THE LARGE MISSLE TEST- | | | ING WITH REPORT. | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|