| Plan Review Notes For Permit 01020279 |
| Permit Number |
01020279 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-21 00:00:00 | ****************DENIED****************** | | | | | | PROVIDE OUTSIDE AIR CALCULATION AS PER | | | ASHRAE 62-89. | | | | | | PROVIDE AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2. | | | | | | DRAWING #M2.1 AHU-3 AND AHU-8 DO NOT | | | INDICATE CFM FOR EVERY DROP. |
|