2001-03-30 00:00:00BUILDING PLAN REVIEW
 01020109
 302 DATURA 2ND FLOOR
 A-SERVICE GLASS & MIRROR
 (954) 561-8213
  
 1)- SBC 1203.1.5 REQUIRES THAT VENTILA-
 TION WILL BE PROVIDED FOR INTERIOR ROOMS
 SKYLIGHTS,VENTS, LOUVERS OR MECHANICAL
 VENTILATION MAY BE SUBSTITUTED FOR
 WINDOWS WHEN APPROVED BY THE BUILDING
 OFFICIAL, PROVIDED ADEQUITE LIGHT &
 VENTILAATION IS PROVED TO MEET THE
 REQUIREMENTS OF THIS CHAPTER.
  
 2)- THE NOTE FOR HANDICAPPED ACCESSIBL-
 ITY IN THE LOUNGE WAS DELETED. NOTES 13
 & 15 DELT WITH THIS ISSUE.THE 1997
 FLORIDA ACCESSIBILITY CODE 4.1.6.2.2
 DEALS WITH THE 20% DISPROPORTIONATE
 COST. 20% OF THE CONTRACT VALUE GOES
 TOWARDS UPGRADING BUILDINGS FOR HANDICAP
 PED ACCESSIBILITY. SINCE THE CONTRACT
 VALUE IS $30,000.00 / $6,000.00 WWOULD
 BE SPENT IN UP GRADES. THE BUILDING DOES
 HAVE AN ELEVATOR FOR VERTICAL ACCESSIBIL
 ITY, (II) AN ACCESSIBILE ROUTE TO THE
 ALTERED AREA, WOULD BE THE NEXT ELEMENT
 TO REVIEW. THIS WOULD INCLUDE THE LOUNGE
 AREA. (III) THE THIRD AREA WOULD BE AT
 LEAST (1) ACCESSIBILE RESTROOM FOR EACH
 SEX OR A SINGLE UNISEX RESTROOM.
  
 SHOW HOW THE $6,000.00 DOLLARS WILL BE
 USED. A COPY OF THE DISPROPORTION COST
 IS ENCLOSED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412