| Plan Review Notes For Permit 01020109 |
| Permit Number |
01020109 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-03-12 00:00:00 | ************ UNSAT ******************** | | | | | | 1)NOTE: PLEASE NOTE THAT PER F.A.C | | | ALL PLANS CONTAINING TITLE BLOCK ARE TO | | | BE SIGNED AND SEALED BY THE | | | ARCH/ENGINEER OF RECORD PER F.S. | | | 471.025 AND 481.221 | | | | | | 2) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) | | | PLEASE CLARIFY IF LOADS ARE SHOWN AT | | | 125%. | | | | | | 3)NOTE: PLEASE SEE SHEET 2, BRANCH | | | CIRCUIT #`SW ARE NOT SHOWN. NEED TO | | | SHOW AND CORRELATE WITH PANEL SCHEDULE | | | THAT IS | | | SUBMITTED. ON FIRST SET OF REVIEW NOTES. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|