Plan Review Notes For Permit 01020109
Permit Number 01020109
Review Stop E
Sequence Number 2
Notes
Date Text
2001-03-12 00:00:00************ UNSAT ********************
  
 1)NOTE: PLEASE NOTE THAT PER F.A.C
 ALL PLANS CONTAINING TITLE BLOCK ARE TO
 BE SIGNED AND SEALED BY THE
 ARCH/ENGINEER OF RECORD PER F.S.
 471.025 AND 481.221
  
 2) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 PLEASE CLARIFY IF LOADS ARE SHOWN AT
 125%.
  
 3)NOTE: PLEASE SEE SHEET 2, BRANCH
 CIRCUIT #`SW ARE NOT SHOWN. NEED TO
 SHOW AND CORRELATE WITH PANEL SCHEDULE
 THAT IS
 SUBMITTED. ON FIRST SET OF REVIEW NOTES.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW