| Notes |
| Date |
Text |
| 2001-02-12 00:00:00 | 1 THE PLANS SHOW WORK ON THE SECOND | | | FLOOR AND THE APPLICATION SAYS THIRD | | | FLOOR.PLEASE CLARIFY. | | | | | | 2 SHOW HOW TENANT SEPARATION WILL BE | | | ACCOMPLISHED AT THE AREA SHOWN AS | | | "EXISTING RECEPTION" NEAR GRID LINES | | | (3) AND (B). | | | SEE SBC 704.3. | | | | | | 3SHOW HOW VENTILATION WILL BE PROVIDED | | | FOR THE INTERIOR ROOMS.SEE SBC 1203. | | | | | | 4THIS BUILDING IS OF TYPE II | | | CONSTRUCTION AND CANNOT USE WOOD STUDS | | | AS SHOWN IN "TYPICAL INTERIOR | | | PARTITION"SEE SBC 609.2.1. AND SBC | | | 604. | | | | | | 5SHOW THE LOUNGE,NOTES 13 AND 15, AS | | | BEING HANDICAP ACCESSIBLE. | | | | | | HAROLD PISKURA | | | 659-8096 X 8219 |
|