| 2001-08-30 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01020102 |
| | 1801 OKEECHOBEE ROAD / 1701 BLDG# 1 |
| | TYPE IV / PROTECTED |
| | FULLY SPRINKLERED |
| | OCCUPANCY: STORAGE |
| | OWNER: PREMIER AIRPORT CENTER, LLP |
| | |
| | 1)- FL. STATE STATUTE 553 / CHAPTER 468 |
| | PART XII CHAPTER 7 OF THE CITY CODE & |
| | THE SBC REQUIRE A RESIDENT INSPECTOR ON |
| | THE SITE. TO DATE NO COMPANY AND INDIVID |
| | UAL HAS MET WITH THE ASSISTANT BUILDING |
| | OFFICIAL DON NEELY TO REGISTER IN THE |
| | PROGRAM. THE INSPECTOR IS REQUIRED TO |
| | SHOW STATE LICENSURE. |
| | |
| | 2)_ ROOF DECK : THE JOB SITE IS LOCATED |
| | IN A FIRE DISTRICT, SHOW MANUFACTURES |
| | SPECIFICATION FOR A CLASS A OR B ROOFING |
| | SYSTEM. |
| | |
| | 3)- ROOF DECK (SYSTEM) SBC 1503.3.2 ROOF |
| | ING SYSTEMS ARE TO BE TESTED FOR THE WIN |
| | D ZONE THAT THE BUILDING IS LOCATED IN. |
| | 110MPH WIND ZONE, SHOW COMPLIANCE EITHER |
| | SBCCI REPORT OR DADE COUNTY, IF NOT |
| | PROVIDED AT TIME OF PERMIT THE ROOFING |
| | PERMIT WILL BE STRUCK & THE CONTRACTOR |
| | WILL HAVE TO COME IN UNDER SEPERATE PER- |
| | MIT WITH REPORT & PAY ADDITIONAL PERMIT |
| | FEES. |
| | |
| | 4)- SBC 104.2.2 ADDITIONAL INFORMATION |
| | REQUIRED. A CURRENT SURVEY WILL BE RE- |
| | QUIRED. |
| | THE SITE IS LOCATED IN A (A-9) |
| | FLOOD ZONE. THE MINIMUM ELEVATION HEIGTH |
| | IS 13'-6" FOR THE FINISH SLAB. A ELEVATI |
| | ON CERTIFICATE WILL BE REQUIRED BEFORE |
| | THE C. O. WILL BE ISSUED. |
| | |
| | 5)- SBC COMPONENTS & CLADDING THE PLANS |
| | DEPICT THAT THERE WILL BE NO SUB-BUCK |
| | FOR WINDOWS & DOORS. THERE SEEMS TO BE |
| | NO DETAIL FOR THE OVERHEAD DOOR. |
| | |
| | 6)- SBC 1606.4.1/ 1707.4.1 AMENDMENTS |
| | ALL GLAZED OPENINGS REQUIRE PRODUCT TEST |
| | ING REPORTS!!!!!!!!!!! TESTING REPORTS |
| | REGAURDLESS OF SHUTTERS IS REQUIRED FOR |
| | WIND SBC 1707.4.1 10 SECOND TEST EQUAL |
| | TO 1.5 TIMES THE DESIGN LOAD. THIS IS |
| | FOR GLASS DOORS, WINDOWS & SKYLIGHTS!!!! |
| | |
| | 7)- SBC 1606.4.1 /1707.4.1 ALL GLAZED OP |
| | ENINGS WILL REQUIRE PRODUCT TESTING FOR |
| | LARGE MISSLE IMPACT TESTING. GLAZED OPEN |
| | INGS THAT HAVEN'T BEEN TESTE FOR THIS |
| | WILL REQUIRE STORM SHUTTER PROTECTION. |
| | THE CITYS' OFFICIAL INTERPRETATION |
| | FOR MISSLE IMPACT PROTECTION HAS A SEC- |
| | TION (#14) REGAURDING STORM SHUTTERS FOR |
| | LARGE PROJECTS. THE BUILDING OFFICIAL |
| | HAS REVIEWED YOUR PROPOSAL & FOUND THAT |
| | IT DOES NOT MEET THE CRITERIA OUTLINED I |
| | N SECTION #14 FOR LARGE PROJECTS. |
| | THERE ARE MULTIPLE SKYLIGHTS THAT |
| | WILL ALSO REQUIRE PRODUCT TESTINGREPORTS |
| | FOR LARGE MISSLE RESISTANCE. |
| | |
| | 8)- THE REFRENCE TO TYPE 1 PLYWOOD USED |
| | FOR THE EXTERIOR CEILING ASSEMBLY WAS CO |
| | RRECTED ON PAGE A-12, THE SAME ASSEMBLY |
| | SHOWS UP ON A-14 DETAILS 12 & 13. |
| | |
| | 9)- THE PAGES THAT ARE VOID NEED TO BE D |
| | ELETED FROM THE PLANS AND THE NEW PAGES |
| | INSERTED BACK INTO THE DOCUMENT. THE |
| | VOIDED PAGES ARE TO BE FOLDED PLACED ON |
| | TOP OF THE PLANS (1 COPY). |
| | |
| | 10)-COUNTY IMPACT FEES ARE TO BE PAID BE |
| | FORE THE ISSUANCE OF THE PERMIT. |
| | |
| | 11)_ ONE OF THE THREE SETS OF PLANS IS |
| | MISSING THE STRUCTURAL DRAWINGS. THIS |
| | SET OF PLANS IS WRAPPED AND NOTED. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X 8412 |