2001-07-17 00:00:00DENIED;
  
 1.PAGE PO.1 (PLUMBING NOTES) NOTE #11
 CALLS FOR CAST IRON PIPE ABOVE GROUND.
 PAGE A-15 (OVERFLOW SCUPPER DETAIL)
 HAS A NOT THAT CALLS FOR PVC PIPE.
 CHANGE NOTE NOTE 11 OR OVERFLOW
 SCUPPER DETAIL.
  
 2.TOTAL RAIN CAULKULATIONS IS 119725 SQ.
 FEET.PLEASE CHECK AND SHOW CAULKS ON
 PLANS I AM NOT AN ENGINEER. THIS IS
 THIRD REQUEST FOR THIS INFORMATION.
 3.PAGE A-5 DOWN SPOUTS FROM PUMP ROOM
 AND ELECTRICAL ROOF AREA SHALL GO TO
 STORM DRAINAGE PER 94 SPC SEC. 1101.2.
  
 4.PAGE PD-4 ROOF DRAIN PIPING UNDER
 GROUND NOT SHOWN. SHOW AND SIZE
 PIPING FROM BUILDING RAIN LEADERS TO
 STORM CATCH BASIN.
  
 5.AIR HAMMER ARREESTERS SHALL BE
 INSTALLED PER MANUFACTORS
 SPECIFICATIONS. SHOULD BE NEAR FIXTURE
  