| 2001-07-31 00:00:00 | BUILDING PLAN REVIEW |
| | 1801 OKEECHOBEE ROAD / 1705 BLDG#1 |
| | PERMIT # 01020102 |
| | TYPE IV/ PROTECTED |
| | FULLY SPRINKLERED |
| | OCCUPANCY: STORAGE |
| | OWNER: PREMIER AIRPORT CENTER, LLP |
| | |
| | NOTE: THIS IS A SHELL PERNIT ONLY, THE O |
| | ONLY USE OF THIS BUILDING WILL BE |
| | "STORAGE", AS PER IMPACT FEES STAMP THAT |
| | WILL BE ASSED. UNDER THE CITYS' PROPERTY |
| | FILE THIS PROPERTY WILL HAVE RESTRICTION |
| | S APPLIED FOR UNDER BUSINESS LICENSES |
| | FOR STORAGE ONLY. BUSINESSES THAT DO NOT |
| | REGISTER WILL PAY PENALTIES FOR NO |
| | OCCUPATIONAL LICENSE PLUS BE ASSESED FOR |
| | ADDITIONAL IMPACT FEES ( FOR OCCUPANCIES |
| | OTHER THAN STORAGE). CITY ADMINISTRATIVE |
| | CODE 104.1 A CHANGE IN OCCUPANCIES |
| | REQUIRES A BUILDING PERMIT, FAILURE TO |
| | SECURE A PERMIT, 4X FEE WILL BE ASSESED. |
| | |
| | 1)- FL STATE STATUTE 553/ CHAPTER 468 |
| | PART XII CHAPTER 7 OF THE CITY CODE & |
| | THE SBC REQUIRE A RESIDENT INSPECTOR ON |
| | SITE AND REGISTERED WITH THE ASSISTANT |
| | BUILDING OFFICIAL, DON NEELY. |
| | |
| | 2)- SBC 903.1 REQUIRES FIRE SPRINKLER |
| | PLANS FROM THE ENGINEER,SIGNED SEALED |
| | AND DATED, 3 SETS OF PLANS WILL BE |
| | REQUIRED. |
| | |
| | 3)- ROOF DECK : PROVISO THE INFORMATION |
| | FOR CLASS A OR B FOR FIRE DISTRICT & |
| | PRODUCT APPROVAL FOR HIGH WIND DISTRICT. |
| | PROVIDE 2 COPIES, THANK YOU. |
| | |
| | 4)- A SURVEY WILL BE REQUIRED,AND ELEVAT |
| | ION CERTIFICATE AFTER THE SLAB IS |
| | POURED.THIS BUILDING IS IN A A-9 FLOOD- |
| | ZONE.THE MINIMUM ELEVATION IS 13'-6" |
| | THIS IS 6" ABOVE THE BASE FLOOD BY CITY |
| | CODE. |
| | |
| | 6)- SBC 1804.2 SOILS TEST REPORT WITH |
| | THE MINIMUM BEARING VALUE. |
| | |
| | 7)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| | BUCK ATTACHMENT FOR WINDOWS, DOORS AND |
| | OVERHEAD DOORS. |
| | |
| | 8)- SBC 1606.4.1 AMEND. 1707.4.1 AMEND. |
| | ALL GLAZED OPENINGS WILL REQUIRE PRODUCT |
| | TESTING REPORTS. TEMPERED GLASS STORE- |
| | FRONT SYSTEMS WILL REQUIRE PRODUCT TEST- |
| | ING, THE STORM SHUTTER SYSTEM WILL RE- |
| | QUIRE APPROVAL FROM THE BUILDING OFFI- |
| | CIALAS IN CASES OF LARGE PROJECTS, SEE |
| | CITYPOLICY FOR GLAZED OPENINGS # 14, |
| | SEE ATTACHED POLICY. THIS WILL BE |
| | REQUIRED BEFORE A PERMIT WILL BE ISSUED |
| | THE PRODUCT APPROVALS FOR WINDOWS & DOOR |
| | CAN BE A "PROVISO", GLAZED OPENINGS WILL |
| | REQUIRE A SEPERATE PERMIT & FEES IF |
| | PRODUCT APPROVALS ARE SUBMITTED AFTER |
| | THE ISSUEANCE OF THE BUILDING PERMIT. |
| | |
| | 9)- STRUCTURAL STEEL SHOP DRAWING ARE |
| | TO BE REVIEWED BY THE ENGINEER OF RECORD |
| | BEFORE THE SUBMITTAL TO THE BUILDING |
| | DEPARTMENT. |
| | |
| | 10)- SSHEET A-12 DETAIL #5 INDICATES A |
| | 5/8" TYPE I PLYWOOD AS PART OF THE |
| | EXTERIOR CEILING ASSEMBLY, TYPE IV BUILD |
| | ING IN A FIRE DISTRICT, NO PLYWOOD ALLOW |
| | ED. |
| | |
| | 11)- COUNTY IMPACT FEES PAID BEFORE THE |
| | ISSUANCE OF A PERMIT. |
| | |
| | BUILING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X 8412 |