| Plan Review Notes For Permit 01020102 |
| Permit Number |
01020102 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-06-09 00:00:00 | PLUMBING PLAN REVIEW"DENIED 2ND X" | | | (1) COMMENTS DATED 02-27-01 HAVE NOT | | | BEEN ADDRESSED. | | | (2) SHTA5,A6,PROVIDE CALCULATIONS FOR | | | SIZING INDIVIDUAL ROOF DRAINS,SPC 94 TAB | | | 1108.1.2, USING FIG 1108.4 RATE OF RAIN | | | FALL, FOR WPB AREA. | | | SECONDARY ROOF DRAINS (SCUPPERS),SHOW | | | CALCULATIONS FOR INDIVIDUAL DRAINS. | | | SPC 94 SEC 1109.1 & FIG 1109.3 RATE OF | | | RAIN FALL,FOR WPB AREA. | | | (3) SHTA 11, METER & PUMP RM ROOFS, | | | PRIMARY & SECONDARY DRAINS NOT SHOWN. | | | (4) SHT P2.1, KEY NOTES,REFERENCES CIVIL | | | DRWGS FOR CONTINUATION OF STORM DRAINS, | | | PLEASE INDICATE WHICH SHTTHIS IS ON. | | | (5) SHT P2.1 & P2.2, SPC 94 SEC 407.1.1 | | | MINIMUM FACILITIES,NUMBER OF EA TYPE OF | | | FIXTURE SHALL BE INSTALLED,USE TAB 407. | | | (6) SHT P0.1 PLBG NOTES 13,18,REFERENCE | | | AIR CHAMBERS,SHOW A DETAIL OF APPROVED | | | AIR CHAMBER AND HOW IT WILL BE RECHARGE- | | | ABLE,ACCESSIBLE SPC 94 SEC 607.8.3 | | | (7) SHTS PP1 TO 4,PROVIDE INFORMATION ON | | | IRRIGATION SYSTEM, SPC 94 SEC 104.3 | | | LOCATION AND TYPE OF BACK FLOW PREVENTER | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS561-659 8096- X8233 |
|