| Plan Review Notes For Permit 01020102 |
| Permit Number |
01020102 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-06-06 00:00:00 | 1) PREVIOUS PLAN REVIEW COMMENTS NOT | | | ADDRESSED. | | | 2) NO FIRE SPRINKLER DRAWINGS OR | | | HYDRAULIC CALCULATIONS PROVIDED WITH | | | PLANS. | | | 3) FIRE ALARM NOTES SECTION INDICATES | | | CLASS B, STYLE C FIRE ALARM CIRCUITS. | | | ONLY CLASS A, STYLE D CIRCUITS OR | | | FULLY ADDRESSABLE FIRE ALARM SYSTEM WILL | | | BE ALLOWED. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|