| 2001-02-27 00:00:00 | DENIED; | | | | | | 1.ROOF DRAINS; SHOW SQ. FT. AREA THAT | | | EACH ROOF DRAIN WILL DRAIN USING 94 | | | SPC CHAPTER 11 AND CHART 1108.4. RAIN | | | FALL IS 4.5 IN. PER. HR.IN THIS AREA, | | | AND 1/2 OF THE TOTAL AREA OF THE | | | PARAPET WALL MUST BE USED TO CALCULATE | | | THE SIZE OF ROOF DRAINS. SHOW CALKS. | | | | | | 2.WHERE DOES RAIN WATER FROM ROOF GO | | | AFTER IT LEAVES THE BUILDING? NO STORM | | | SEWER, SANITARY SEWER, OR WATER | | | SERVICE IS SHOWN ON SITE PLANS. | | | | | | 3.AREA WHERE PLUMBING MIGHT BE INSTALLED | | | SHOULD HAVE 6 X 4 YEE'S INSTALLED IN | | | THE BUILDING DRAIN AT TIME OF INSTALL- | | | ATION. THIS INSURES THE INTEGRITY OF | | | THE BUILDING DRAIN. | | | | | | 4.ONE 3" VENT SHALL BE INSTALLED THRU | | | ROOF 94 SPC SEC.904.3.1. | | | | | | 5.WATER MAIN SHOULD HAVE FUTURE DROPS | | | WITH SHUTOFF VALVES WHERE PLUMBING MAY | | | BE INSTALLED. |
|