Plan Review Notes
Plan Review Notes For Permit 01020018
Permit Number 01020018
Review Stop B
Sequence Number 1
Notes
Date Text
2001-02-08 00:00:00NORTHWOOD UNIVERSITY
 2600 N MILITARY TRAIL
 PERMIT # 01020018
 1)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, BUILDING CODE SUMMARY IS USING
 THE WRONG CODE, WE USE THE 1997
 STANDARD BUILDING CODE AND THE 1997
 EDITION OF THE FL ACCESSIBILITY CODE.
 THE CONSTRUCTION TYPES LISTED ON THE
 PLAN DO NOT MATCH THE CONSTRUCTION TYPES
 THAT WE CURRENTLY USE IN THE STANDARD
 BUILDING CODE. THE OTHER ISSUE THAT MAY
 CAUSE A ISSUE WOULD BE THE "YES" TO
 BEING LOCATED IN A FIRE DISTRICT.
 2)- THE PLANS (A-1) INDICATE A NEW
 STOREFRONT SYSTEM, IS THIS SYSTEM ON THE
 INTERIOR OF THE STRUCTURE, OR IS THIS
 A EXTERIOR WALL? GLAZYING SYSTEMS ON THE
 EXTERIOR WILL REQUIRE APPROVAL REPORTS
 FOR HIGH WIND AREAS. THE CITY ACCEPTS
 DADE COUNTY PRODUCT APPROVALS OR REPORTS
 FROM THE STANDARD BUILDING CODE CONGRESS
 INTERNATIONAL (SBCCI).
 3)- THERE IS A NOTE ON THE PLAN "LOWER
 LOBBY" IS THERE A CHANGE IN ELEVATION?
 4)- FL ACESSIBILITY CODE 5.2 COUNTERS
 & BARS; SATISFY THIS REQUIREMENT.
 5)- FL ACCESSIBILITY CODE 5.4 DINING
 AREAS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 PHONE (561)659-8096 EX 8412