Plan Review Notes
Plan Review Notes For Permit 01011457
Permit Number 01011457
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-02-02 00:00:001) SMOKE DETECTORS WHEN INSTALLED ARE
 TO BE A MINIMUM OF THREE FEET FROM
 AIR CONDITIONER DIFFUSERS.
 2) THE COMBINATION SYSTEM FIRE/SECURITY
 SHALL MEET ALL OF THE REQUIREMENTS OF
 NFPA 72, SECTION 2-4.7 COMBINATION
 SYSTEM. ALSO NFPA 72, SECTION 2-4.7.1
 AND 2-4.7.2 ARE TO BE FOLLOWED.
 3) SYSTEM TO BE MONITORED BY A LICENSED
 UL LISTED CENTRAL STATION APPROVED BY
 THE FIRE RESCUE DEPARTMENT.
 4) ANY HOOD DUCT AND EXTINGUISHING
 SYSTEMS CONTAINED IN THE BUILDING ARE
 TO BE CONNECTED TO THE FIRE ALARM
 SYSTEM.
 5) PLEASE EXPLAIN SMOKE DETECTOR
 ARRANGEMENT FOR HOLD-OPEN DOORS IN
 BUILDING. PLEASE REFER TO NFPA 72,
 SECTION 5-11.7.4 SMOKE DETECTORS FOR
 DOOR RELEASE SERVICE. PLEASE SEE
 5-11.7.4.1-5-11.7.4.4.1.
 6) DUCT SMOKE DETECTOR INSTALLATION TO
 COMPLY WITH NFPA 72.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved