| Plan Review Notes For Permit 01011378 |
| Permit Number |
01011378 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-15 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRNET PER 110-9. | | | PANEL AIC RATINGS WERE SUBMITTED BUT | | | NOT FOR MAINS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION. IF | | | THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|