Plan Review Notes
Plan Review Notes For Permit 01011346
Permit Number 01011346
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-30 00:00:001) THE FIRE ALARM SYSTEM WHEN ACTIVATED
 IS TO BE AUDIBLE THROUGHOUT.
 2) SYSTEM TO BE CLASS A, STYLE D WIRED.
 3) DUCT SMOKE DETECTORS WHEN ACTIVATED
 IS TO CAUSE THE FIRE ALARM SYSTEM TO
 ACTIVATE AND SHUT DOWN THE AIR
 CONDITIONING EQUIPMENT.
 4) SMOKE DETECTORS WHEN INSTALLED ARE TO
 BE A MINIMUM OF THREE FEET FROM AIR
 CONDITONER DIFFUSERS.
 5) SYSTEM TO BE MONITORED BY A LICENSED
 UL LISTED CENTRAL STATION APPROVED BY
 THE FIRE RESCUE DEPARTMENT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910