| Plan Review Notes For Permit 01011330 |
| Permit Number |
01011330 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-30 00:00:00 | 1) SMOKE DETECTORS WHEN INSTALLED ARE TO | | | BE AT LEAST THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 2) SYSTEM TO BE CLASS A, STYLE D. | | | 3) THE FIRE ALARM AND FIRE SPRINKLER | | | SYSTEM TO BE MONITORED BY A LICENSED UL | | | LISTED CENTRAL STATION APPROVED BY THE | | | FIRE RESCUE DEPARTMENT. | | | 4) SYSTEM AFTER INSTALLATION IS TO BE | | | TESTED WITH FIRE RESCUE PERSONNEL. | | | 5) PLEASE PROVIDE HORN-STROBE DEVICES | | | IN WORK BAYS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|