| Plan Review Notes For Permit 01011254 |
| Permit Number |
01011254 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-01 00:00:00 | DENIED | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) PROVIDE ENGINEERING FOR BUTT GLASS | | | ASSEMBLIES PER 1997 SBC 2406.2. | | | | | | 4) PROVIDE KEY PLANS AND INSTALLATION | | | SCHEDULE INDICATING THE SPECIFIC TYPES | | | OF ANCHORS TO BE USED FOR STORM PANELS. | | | | | | 5) PROVIDE 2 CURRENT COMPLETE COPIES OF | | | SBCCI OR METRO DADE PRODUCT APPROVALS | | | FOR: | | | - ARCHED FIXED GLASS WINDOWS | | | - FRENCH DOORS WITH SIDELITES (ASSEMBLY) | | | | | | 6) ON SHEET A-2,FOOTING F5 IS NOT LISTED | | | ON THE FOOTING SCHEDULE AND F4 DOES NOT | | | LIST THE NUMBER OF #5 BARS REQUIRED. | | | PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|