| 2001-02-06 00:00:00 | ******************* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRNET PER 110-9. |
| | |
| | 2) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | |
| | 3) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | |
| | 4) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | |
| | 5) NOTE: PLEASE SHOW ALL OUTLETS |
| | SERVINGKITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECT--ED PER 210-8-A-6. |
| | |
| | 6)NOTE: PLEASENOTE, PLANS ONLY SHOW |
| | ONE MAIN AND ONE PANELSCHEDULE. |
| | PLEASE CORRLATE. |
| | |
| | 7)NOTE: PLEASE NOTE THAT THE RISER |
| | DIAGRAMS AND PANEL SCHEUDULES DO NOT |
| | CORRELATE. |
| | TOTALS/240AMPS ??? |
| | 200A EQUIPMENT WITH OVER 200A LOADS?? |
| | 250A PANELS ON PANEL SCH AND 200A ON |
| | RISER.???? |
| | 150A PANEL AND 100A ON RISER??? |
| | WHAT SIZE IS METERCAN?? |
| | 104A LOAD ON 100A MLO OR 150A??? |
| | ETC ETC,, |
| | |
| | 8) NOTE: PLEASE SHOW GROUNDING |
| | ELECTRODE GOING TO BLDG STEEL REQ`D |
| | PER 250-50 |
| | |
| | 9)NOTE: MISSING HALL OUTLET PER 210-52H |
| | |
| | 10)NOTE: MISSING WHIRLPOOL ON PANEL |
| | SCHEDULE THAT IS SHOWN ON PLAN?? |
| | |
| | PLEASE SUBMIT ALL THEABOVE |
| | INFORMATIONFOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS PLEASE CALL. |
| | |