Plan Review Notes
Plan Review Notes For Permit 01011254
Permit Number 01011254
Review Stop E
Sequence Number 1
Notes
Date Text
2001-02-06 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 2) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 3) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
  
 5) NOTE: PLEASE SHOW ALL OUTLETS
 SERVINGKITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
  
 6)NOTE: PLEASENOTE, PLANS ONLY SHOW
 ONE MAIN AND ONE PANELSCHEDULE.
 PLEASE CORRLATE.
  
 7)NOTE: PLEASE NOTE THAT THE RISER
 DIAGRAMS AND PANEL SCHEUDULES DO NOT
 CORRELATE.
 TOTALS/240AMPS ???
 200A EQUIPMENT WITH OVER 200A LOADS??
 250A PANELS ON PANEL SCH AND 200A ON
 RISER.????
 150A PANEL AND 100A ON RISER???
 WHAT SIZE IS METERCAN??
 104A LOAD ON 100A MLO OR 150A???
 ETC ETC,,
  
 8) NOTE: PLEASE SHOW GROUNDING
 ELECTRODE GOING TO BLDG STEEL REQ`D
 PER 250-50
  
 9)NOTE: MISSING HALL OUTLET PER 210-52H
  
 10)NOTE: MISSING WHIRLPOOL ON PANEL
 SCHEDULE THAT IS SHOWN ON PLAN??
  
 PLEASE SUBMIT ALL THEABOVE
 INFORMATIONFOR REVIEW. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372