Plan Review Notes For Permit 01011254
Permit Number 01011254
Review Stop B
Sequence Number 1
Notes
Date Text
2001-06-14 00:00:00*************BUILDING UNSAT*************
 REVISION TO ADD CHIMNEY SURROUND
  
 ADDITIONAL INFORMATION IS REQUIRED
 PER 97 SBC SECT.102.4.1.
  
 1) PROVIDE DETAIL OF CEILING INSULATION
 AT PROPOSED CHIMNEY THAT COMPLIES WITH
 FL ENERGY CODE.
  
 2) INDICATE IF CHIMNEY IS TO BE
 FUNCTIONING OR NOT. IF FUNCTIONAL,
 INDICATE PURPOSE FOR WHICH IT WILL BE
 USED AND PROVIDE ALL PERTINENT
 INFORMATION FOR FLUE AND APPLIANCE.
  
 3) INDICATE OVERALL HEIGHT OF THIS
 STRUCTURE.
  
 4) INDICATE WALL AND ROOFING MATERIALS.
 (COMPONENTS AND CLADDING)
  
 5) INDICATE FIREBLOCKING &
 DRAFTSTOPPINGBETWEEN CHIMNEY AND ATTIC
 SPACE.
  
 6) PROVIDE STRUCTRAL DESIGN
 CALCULATIONS FOR BEARING, UPLIFT AND
 MOMENT.
  
 7) INDICATE THE TYPE AND LOCATION OF
 CONNECTORS USED TO SUPPORT AND PROVIDE
 CONTINOUS TIE TO STRUCTURE.
  
 8) PROVIDE STRUCTURAL ANALYSIS OF
 TRUSSES TO ENSURE THEIR ABILITY TO
 HANDLE THE ADDITIONAL LOADS THAT WILL
 BE IMPOSED BY THE CHIMNEY SURROUND.
  