Plan Review Notes
Plan Review Notes For Permit 01011253
Permit Number 01011253
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2001-04-10 00:00:001) SMOKE DETECTORS WHEN INSTALLED SHALL
 BE A MINIMUM OF THREE FEET FROM ANY
 AIR CONDITIONING DIFFUSERS.
 2) DUCT SMOKE DETECTORS ARE REQUIRED IN
 HVAC SYSTEMS OVER 2000 CFM'S. WHEN
 ACTIVATED, DUCT SMOKE DETECTORS SHALL
 CAUSE THE FIRE ALARM SYSTEM TO ACTIVATE
 AND CAUSE ASSOCIATED HVAC EQUIPMENT TO
 SHUT DOWN.
 3) THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS ARE TO BE MONITORED BY A
 LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 4) SYSTEM IS TO BE TESTED IN THE
 PRESENCE OF FIRE RESCUE PERSONNEL.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910