| Plan Review Notes For Permit 01011250 |
| Permit Number |
01011250 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-30 00:00:00 | ******************** UNSAT ************* | | | | | | | | | 1)NOTE: PLANS SUBMITTEDCANNOT BE DONE | | | IN PENCIL PER F.A.C AND COUNTY WIDE | | | AMENDMENTS. | | | 2)NOTE: ALSO PLEASE NOTE OUTLETS AND | | | SPACING IN KITCHEN ARE TO BE SHOWN. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRNET PER 110-9. | | | | | | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 5)NOTE: PLEASE SUBMIT PANEL SCHEDULE(S) | | | SHOWING SCHEDULE W/ MIN REQ`D CIRCUITS | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS PLEAS | | | E CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|