| 2001-01-26 00:00:00 | 1) FIRE ALARM SYSTEM TO BE CLASS A, | | | STYLE D OR FULLY ADDRESSABLE. | | | 2) SMOKE DETECTORS TO BE INSTALLED A | | | MINUMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 3) DUCT SMOKE DETECTORS REQUIRED IN | | | SYSTEMS OVER 2000 CFM. WHEN ACTIVATED | | | THESE DEVICES ARE TO SHUT DOWN AIR | | | HANDLING EQUIPMENT AND ACTIVATE THE FIRE | | | ALARM SYSTEM. | | | 4) ADDITIONAL DEVICES WILL BE REQUIRED | | | WHEN THE INDIVIDUAL TENANT SPACES ARE | | | FITTED UP. | | | 5) HORN-STROBES ARE TO BE MOUNTED | | | BETWEEN 80 AND 96 INCHES FROM THE FLOOR. | | | 6) MANUAL PULL STATIONS ARE TO BE | | | MOUNTED BETWEEN 3 1/2 TO 4 1/2 FEET | | | ABOVE THE FOOR. | | | 7) SYSTEM TO BE TESTED WITH A MEMBER OF | | | THE FIRE RESCUE DEPARTMENT. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|