Plan Review Notes
Plan Review Notes For Permit 01011197
Permit Number 01011197
Review Stop M
Sequence Number 1
Notes
Date Text
2001-02-22 00:00:00PROVISO:DUCT SMOKE DETECTORS MUST BE
 TESTED TO SHOW COMPLIANCE WITH NFPA
 90A-12, 4.4.4.3, FAN SHUT DOWN WITH
 NOTIFICATION TO NORMALLY OCCUPIED AREAS
 BY ALARM/STROBE.
  
 AHU-5 IN THE COPY/FILE WORKROOM (ROOM
 234), SHALL HAVE ACCESS/CLEARANCE FOR
 MAINTENANCE AND SERVICE AS PER 1997 SMC
 304.2.1 AND 304.2.3.
  
 REVIEW DONE UNDER MASTER 01011195.