| Plan Review Notes For Permit 01011195 |
| Permit Number |
01011195 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-29 00:00:00 | **************DENIED******************** | | | 1. PROVIDE INFORMATION ON EQUIPMENT TO | | | BE USED. NO AC-2 DRAWING INCLUDED AS | | | CALLED FOR ON SCHEDULE OF DRAWINGS. | | | 2. ALL WALLS APPEAR TO GO FLOOR TO | | | CEILING. PROVIDE RETURN AIR TRANSFER | | | FOR AHU,S FROM ROOMS. | | | 3. PROVIDE LEGEND, PLAN SHOWS EXISTING | | | CHW IS THIS CONDENSER WATER OR CHILLED | | | WATER? PLAN CALLS FOR CONDENSATE DRAIN | | | AND EMERGENCY PAN. PROVIDE INFORMATION | | | ON SECONDARY PIPIMG OR FLOAT SWITCH. | | | 4. NOTE: NO COMBUSIBLE MATERIALS IN | | | RETURN AIR PLENUM ABOVE CEILING AREA. | | | 5. PROVIDE INFORMATION ON FAN SHUT DOWN | | | BY DUCT SMOKE DETECTOR FOR ALL | | | EQUIPMENT (COMMON PLENUM). | | | 6. NOTE THIS PLAN CANNOT BE CROSS | | | REFERENCED TO SHELL PLAN BECAUSE THE | | | INFORMATION PROVIDED ON THIS PLAN DOES | | | NOT CORRESPOND TO THE INFORMATION ON THE | | | SHELL PLAN. |
|