Plan Review Notes
Plan Review Notes For Permit 01011170
Permit Number 01011170
Review Stop P
Sequence Number 2
Notes
Date Text
2001-04-16 00:00:00DENIED;
  
 1.TRAP PRIMER REQUIRED FOR FLOOR DRAIN.
  
 2.PAN DRAIN SHALL BE 1" 507.8.2
  
 3.PRESSURE RELIEF VALVE TO DISCHARGE TO
 DRAINAGE SYSTEM WERE IT CAN BE READLY
 OBSERVED BY THE BUILDING OCCUPANTS
 SPC 507.8.4.
  
 4.WATER HEATER SHALL BE READLY ACCESIBLE
 501.7.