| Plan Review Notes For Permit 01011170 |
| Permit Number |
01011170 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-02 00:00:00 | ******************UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE, COVER SHEET SHOWS | | | E- SHEETS AND NONE WERE SUBMITTED?? | | | PLEASE SUBMIT. | | | SHEET A2.01 DOES NOT HAVE ENOUGH | | | ELECTRICAL DETAIL FOR REVIEW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|