| 2001-06-07 00:00:00 | ********************DENIED************** | | | | | | | | | DID RATING OF WALL CHANGE...IF SO, WAS | | | IT SUBMITTED TO BUILDING PLAN REVIEW. | | | | | | DAMPER MAY NOT BE REMOVED UNLESS IT | | | MEETS THE REQUIREMENTS OF 1997 SMC | | | 610.1.3 ITEM 3. | | | | | | 1.DUCT SHALL NOT EXCEED 100 SQ INCHS. | | | 2.SHALL BE OF 0.0217" MIN. STEEL. | | | 3.DUCT SHALL CONTINUE W/NO OPENINGS | | | FOR 5' FROM THE RATED WALL & | | | 4.DUCT SHALL BE INSTALLED ABOVE | | | CEILING. |
|