2001-06-07 00:00:00********************DENIED**************
  
  
 DID RATING OF WALL CHANGE...IF SO, WAS
 IT SUBMITTED TO BUILDING PLAN REVIEW.
  
 DAMPER MAY NOT BE REMOVED UNLESS IT
 MEETS THE REQUIREMENTS OF 1997 SMC
 610.1.3 ITEM 3.
  
 1.DUCT SHALL NOT EXCEED 100 SQ INCHS.
 2.SHALL BE OF 0.0217" MIN. STEEL.
 3.DUCT SHALL CONTINUE W/NO OPENINGS
 FOR 5' FROM THE RATED WALL &
 4.DUCT SHALL BE INSTALLED ABOVE
 CEILING.