Plan Review Notes
Plan Review Notes For Permit 01011146
Permit Number 01011146
Review Stop P
Sequence Number 1
Notes
Date Text
2001-02-04 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) SHT A-1
 PLUMBING PLAN REVIEWDENIED
 CODE REFERENCES SPC 94,FACBC 97
 (1A) SHT.A-1 BREAK RM.#010 SEC.4.13.6
 MANEUVERING CLEARANCE AT DOORS.
 SEC. 4.24.5 DOOR SWING INTO CLEAR FLOOR
 SPACE OF SINK,
 (B) BREAK RM. SINK SEC. 4.24 MAX HIGTH
 34" FF, CLEAR FLR SPACE 30"X48" KNEE
 CLEARANCE 19".
 (2A) SHT M-1 SEC.303,LIST MATERIALS,
 SPECIFICATIONS.
 (B) WATER PIPE RISER,AIR CHAMBERS TO BE
 READLY ACCESSIBLE,RECHARGEABLE,
 SEC 607.8.3
 (C) SANITARY RISER SEC 908.1 EACH
 FIXTURE TRAP SHALL HAVE A PROTECTING
 VENT. W/C & F/D, RM 005.
 (D) WATER HEATERS ABOVE CEILING,SHALL BE
 READLY ACCESSIBLE SEC 501.7, SHOW A
 DETAIL OF A WORKING PLATFORM WITH A
 FIXED SHIPS LADDER IN PLACE.
 END OF COMMENTS,CONTACT PAUL SCHMITZ
 561-659-8096 X 8233