| Plan Review Notes For Permit 01011146 |
| Permit Number |
01011146 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-04 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | (1) SHT A-1 | | | PLUMBING PLAN REVIEWDENIED | | | CODE REFERENCES SPC 94,FACBC 97 | | | (1A) SHT.A-1 BREAK RM.#010 SEC.4.13.6 | | | MANEUVERING CLEARANCE AT DOORS. | | | SEC. 4.24.5 DOOR SWING INTO CLEAR FLOOR | | | SPACE OF SINK, | | | (B) BREAK RM. SINK SEC. 4.24 MAX HIGTH | | | 34" FF, CLEAR FLR SPACE 30"X48" KNEE | | | CLEARANCE 19". | | | (2A) SHT M-1 SEC.303,LIST MATERIALS, | | | SPECIFICATIONS. | | | (B) WATER PIPE RISER,AIR CHAMBERS TO BE | | | READLY ACCESSIBLE,RECHARGEABLE, | | | SEC 607.8.3 | | | (C) SANITARY RISER SEC 908.1 EACH | | | FIXTURE TRAP SHALL HAVE A PROTECTING | | | VENT. W/C & F/D, RM 005. | | | (D) WATER HEATERS ABOVE CEILING,SHALL BE | | | READLY ACCESSIBLE SEC 501.7, SHOW A | | | DETAIL OF A WORKING PLATFORM WITH A | | | FIXED SHIPS LADDER IN PLACE. | | | END OF COMMENTS,CONTACT PAUL SCHMITZ | | | 561-659-8096 X 8233 |
|