Plan Review Notes
Plan Review Notes For Permit 01011146
Permit Number 01011146
Review Stop E
Sequence Number 1
Notes
Date Text
2001-02-01 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 FOR SERVICE.215-5
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IFTHERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)