| Plan Review Notes For Permit 01011120 |
| Permit Number |
01011120 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-02-28 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE WHEN PLANS WERE | | | FIRST SUBMITTED NO ELECTRICAL SERVICE | | | CHANGE WAS SUBMITTED. PLEASE NOTE, NOW | | | THERE IS MORE INFORMATION THAT IS | | | NEEDED. | | | NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2)NOTE: PLEASE SEE LOAD CALCULATION | | | SUBMITTED. PLEASE NOTE TWO(2) SM APPL | | | CIRCUITS ARE REQ`D. | | | | | | 3)NOTE: PLEASE CLARIFY THE EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | | PANEL. PER 250-122 | | | | | | 4) NOTE: PLEASE SHOW GROUNDING | | | ELECTRODEGOING TO BUILDING STEEL OF NEW | | | BLDG TO BE BONDED. PER 250-50. | | | | | | 5)NOTE: PLEASE NOTE THAT ALL ITEMS THAT | | | WERE REDLINED ON FIRST REVIEW NEED TO BE | | | DRAWN IN IN THE MANNER IN WHICH THE REST | | | OF THE PLANS ARE DRAWN.104.2 ADMIN | | | CODE. | | | | | | PLEASE SHOW LOCATION OF NEW EQUIPMENT IF | | | KNOWN AT THIS TIME. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|