| 2001-01-29 00:00:00 | CONTRACTOR: GEN-X CONSTRUCTION |
| | 2419 S DIXIE HWY |
| | 1)- FL. ACCESIBILITY CODE 4.1.6.1(C)- |
| | IF ALTERATIONS OF SINGLE ELEMEMNTS, WHEN |
| | CONSIDERED TOGETHER, AMOUNT TO AN ALTER- |
| | ATION OF A ROOM OR SPACE IN A BUILDING |
| | OR FACILITY, THE ENTIRE SPACE SHALL BE |
| | MADE ACCESIBLE. THE MENS RESTROOM DOES |
| | NOT MEET THE CURENT HANDICAPPED ACCESS- |
| | IBILITY CODE. |
| | 2)-FL. ACCESSIBILITY CODE 4.1.6.2.2- |
| | DISPROPORTIONATE COST SEE ATTACHMENT OF |
| | PRIORITIES IN CHOOSING WHAT ELEMENTS |
| | GIVE THE GREATEST ACCESS IN THE FOLLOW- |
| | ING ORDER.20 %OF CONTTRACT VALUE IS |
| | WHAT IS REQUIRED PER IMPROVEMENT. |
| | 3)- FL ACC. 4.13.5 MENS RESTROOM WILL |
| | REQUIRE A MINIMUM CLEAR OPENING OF 32". |
| | 4)- FL ACC.4.13.6 MANEUVERING CLEARANCES |
| | AT DOORWAYS, THERE ISN'T ENOUGH CLEAR |
| | TURNING SPACE TO MEET THE 60" DIAMETER |
| | SPHERE. |
| | 5)- FL ACC 4.13.9 DOOR HARDWARE REQUIRES |
| | LEVER-OPERATED MECHANISMS,PUSH-TYPE MECH |
| | ANISMS AND U-SHAPED HANDLES ARE ACCEPT- |
| | ABLE DESIGNS. |
| | 6)- FIRE ZONE: THIS BUILDING IS LOCATED |
| | IN A FIRE ZONE. F102.1 NO WOOD IS ALLOW- |
| | ED INEXTERIOR WALLS (F102.1) NO WOOD |
| | ALLOWED IN EXTERIOR WALLS.SEE SEC. 1/3. |
| | 7)- SEC. A-3, 2/3: F105.12 WOOD VENEERS |
| | DO NOT CONFORM WITH SBC 1403.6.7. |
| | 8)- SBC 1606.2A VELOCITY PRESSURE FOR |
| | WINDOWS NOT GIVEN. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |