| 2001-02-21 00:00:00 | PERMIT # 01010883 | | | 2855 CUYAHOGA LANE | | | MINICON CONSTRUCTION | | | 683-6179 | | | 1)- FL ENERGY FORM 600C-97 | | | A)-GLASS AREA CHECK AREA FIGURES, | | | 16'0"X 6'8" GLASS DOORS ALONE ARE 106.5' | | | B)- MASONARY WALL INSULATION ON FORM IS | | | 5.0 AND ON PLAN A 4.2R? | | | | | | 2)- 1606.4.1 THE PRODUCT APPROVAL REPORT | | | SUBMITTED IS FOR SINGLE HUNG WINDOWS, | | | NOT FOR SLIDING GLASS DOORS. | | | | | | 3)- FL. S. S. 489.113 (B) MUST SUB- | | | CONTRACT THE ROOFING UNLESS IT IS WOOD | | | SHINGLES, WOOD SHAKES, OR ASPHALT OR | | | FIBERGLASS SHINGLE ROOFING ON A NEW | | | BUILDING OF HIS OWN CONSTRUCTION. | | | | | | 4)- PLANS MUST GO TO THE PALM BEACH | | | COUNTY BUILDING DEPARTMENT TO BE ASSESS- | | | ED FOR ADDITIONAL IMPACT FEES.COUNTY | | | STAMP REQUIRED ON PLANS. | | | | | | 5)- THE CONTRACTOR IS REQUIRED TO SIGN | | | THE APPLICATION ON PAGE 3 OF THE APPLICA | | | TION. | | | | | | 6)- THE ROOF FRAMING PLAN DOESN'T GIVE | | | THE UPLIFT VALUES FOR THE LEFT SIDE OF | | | THE PARALLAM BEAM, VALUES TO BE RESTRAIN | | | ED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|