| Plan Review Notes For Permit 01010767 |
| Permit Number |
01010767 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-24 00:00:00 | ************ PROVISO *********** | | | | | | 1)NOTE: PLEASE PROVIDE LAYOUT OF NEW | | | SD`S INSIDE AND OUTSIDE ALL SLEEPING | | | ROOMS PER NFPA-72 2-2.1.1.1. | | | 2)NOTE: PLEASE SHOW FLOOR LAYOUT OF | | | DEVICES BEING CHANGED OUT AND NEW GFI | | | LOCATIONS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ANY INSPECTION IS CALLED | | | IN. IF THERE ARE ANY QUESTIONS PLEASE | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|