| 2001-11-15 00:00:00 | REVISION DENIED |
| | |
| | 1) PROVIDE EMERGENCY ESCAPE AND EXIT |
| | OPENING IN SECOND FLOOR GUEST ROOM PER |
| | 97 SBC SECTION 1005.4.1. THE MINIMUM |
| | NETCLEAR OPENING AREA SHALL BE 5.7 |
| | SQ.FT., THE MINIMUM NET CLEAR OPENING |
| | HEIGHT OF 24" AND WIDTH OF 20" (SECT. |
| | 1005.4.4) & SILL HEIGHT OF NOT MORE |
| | THAN 44" |
| | (SECT. 1005.4.3). |
| | |
| | 2) INDICATE ACCESS TO ATTIC ACCESS TO |
| | COMPLY WITH 97 SBC SECT. 2309.6. |
| | |
| | 3)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - STRUCTURAL WINDOW MULLIONS |
| | - STORM PANELS FOR FRENCH DOORS |
| | |
| | 4) EXTERIOR EXITWAY STAIRS: |
| | - EXTERIOR STAIRS SHALL BE SEPARATED |
| | FROM THE INTERIOR OF THE BUILDING BY |
| | WALLS WITH A FIRE RESISTANCE RATING OF |
| | NOT LESS THAN ONE HOUR, WITH FIXED OR |
| | SELF-CLOSING OPENING PROTECTIVES AS |
| | REQUIRED FOR ENCLOSED STAIRS. THIS |
| | PROJECTION SHALL EXTEND VERTICALLY FROM |
| | THE GROUND TO A POINT 10 FT. ABOVE THE |
| | TOPMOST LANDING OR THE ROOF LINE, |
| | WHICH-EVER IS LOWER AND HORIZONTALLY 10 |
| | FT. |
| | FROM EACH SIDE OF THE STAIRWAY. |
| | OPENINGSWITHIN THE 10 FT. HORIZONTAL |
| | EXTENSION |
| | OF THE PROTECTED WALLS BEYOND THE |
| | STAIRWAY SHALL BE EQUIPPED WITH FIXED |
| | 3/4- HOUR ASSEMBLIES. |
| | (97 SBC SEC. 1006.2.4) THE NEW WINDOWS |
| | AND DOORS AT STAIRS MUST COMPLY. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |
| 2001-10-30 00:00:00 | ************BUILDING PROVISO************ |
| | |
| | 1) PROVIDE MANUFACTURES SPECIFICATIONS, |
| | UL LISTING INFORMATION, STRUCTURAL |
| | DRAWINGS AND ELEVATION DRAWINGS FOR |
| | VENTLESS FIRE BOX PRIOR TO INSTALLATION. |
| | INSTALLATION MUST COMPLY WITH CHAPTER 9 |
| | OF THE 97 STANDARD MECHICAL CODE. |
| | A SEPARATE GAS PERMIT WILL BE REQUIRED |
| | IF USING A GAS APPLIANCE IN FIRE BOX. |
| | |
| | 2) PROVIDE PRODUCT APPROVALS FOR DOUBLE |
| | INSWING ENTRY DOORS WITH SIDELITES, |
| | PRIOR TO INSTALLATION. UNIT MUST COMPLY |
| | WITH LARGE MISSLE IMPACT PROTECTION |
| | REQUIREMENTS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |
| | |
| | REVISION WAS RESUBMITTED ON 11-8-01 FOR |
| | PLBG. AND ELEC. THE ITEMS REQUESTED IN |
| | ABOVE PROVISO WERE ADDRESSED. |
| | RM 11-15-01 |