| 2001-01-25 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT PER F.A.C SEC. |
| | 481.221 PLANS ARE TO BE SIGNED AND |
| | SEALED BY THE ARCHITECT OF RECORD. |
| | PLEASE NOTE THAT ALL SHEETS THAT |
| | CONTAIN TITLE BLOCK. |
| | |
| | 2) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 3) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. UPSTAIRS |
| | |
| | 4) NOTE: PLEASE SHOW GROUNDING |
| | ELECTRODEGOING TO BUILDING STEEL AND |
| | COLD WATER |
| | PER 250-50. |
| | |
| | 5) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 6) NOTE: PLEASE SHOW ALL OUTLETS |
| | SERVINGKITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECT--ED PER 210-8-A-6. |
| | |
| | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRNET PER 110-9. |
| | |
| | 8)NOTE: PLEASE SHOW AND CLARIFY WHERE |
| | POWER FOR NEW GARAGE IS COMING FROM??? |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |