Plan Review Notes
Plan Review Notes For Permit 01010696
Permit Number 01010696
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-25 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`SON PLANS, PLEASE CORRELATE WITH
 PANEL SCHEDULES.
  
 2)NOTE: NOT ENOUGH INFORMATION ON PANEL
 SCHEDULES.
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE. ROOF TOP? EXISTING?
  
 4)NOTE: PLEASE NOTE MEANS OF DISCONNECT
 ON LOAD SIDE OF TRANSFORMER REQ`D FOR
 SEPARATELY DERIVED SYSTEM.
  
 5)NOTE: PLEASE SHOW GROUNDING FOR
 TRANSFORMER AND ENTIRE ELECTRICAL
 SERVICE.
 GENERATOR ETC.
  
 6)NOTE: PLEASE SHOW VOLTAGES ON ALL NEW
 EQUIPMENT AND PANELS WITH NEW ITEMS.
 PLEASE SEE F.A.C. SECTION 553-79-6A
 ALL WORK CONTAINING 277/480 ON SERVICES
 ARE TO BE SIGNED AND SEALED BY A "PE"
  
 7)NOTE: PANEL SCSCHEDULES ARE TO BE
 MOREDETAILED.
  
  
 8)NOTE: SUBMIT LOAD CALCULATIONS, NOTE
 ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%. (LIGHTING) LARGEST MOTOR) ECT.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372