Plan Review Notes
Plan Review Notes For Permit 01010669
Permit Number 01010669
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-29 00:00:002415 MEDINA WAY
 O/B WALSH, THOMAS
 1)- SHEET A-4 DETAIL #6 NOTE STUCCO OVER
 WIRE LATH, SBC 103.7.2.1 A 6" FULL CLEAR
 INSPECTION SPACE OF THE FOUNDATION
 SIDEWALL IS REQUIRED BETWEEN WOOD SIDING
 STUCCO WITH WIRE LATH DOWN TO THE TOP OF
 THE SOD, MULCH OR SOIL.
 2)- SBC 104.2.2- ADDITIONAL INFORMATION
 REQUIRED:
 A)- SHEET A-3 DETAIL #5 SHOWS A DETAIL
 OF THE 6"X6" POST ANCHORED TO THE
 FOUNDATION, THIS DETAIL WILL MEAN THAT
 THE POST WILL NOT SIT ON THE STEM WALL
 BUT WILL BE BURIED IN THE SOIL APPR. 8"?
 B)- SHEET A-4 DETAIL #6, WILL REQUIRE
 OVERFLOW SCUPPERS ON THE FLAT DECK WITH
 PARAPET WALLS, (SBC 1517.6.4.3).
 C)- SBC 1804.6.2.2- CRAWL SPACE
 REQUIRES ACCESS OPENINGS.
 D)- DISCREPANCY, SHEEET A-1 VS A-5.
 THE SHEET A-5 SHOWS DETAILS #2/4 WITH
 NOTE BEDROOM #3 EXISTING WHILE SHEET A-1
 PROPOSED 2 STORY ADDITION?
 3)- SBC 1707.5, PRODUCT APPROVAL IS RE-
 QUIRED FOR ROOF TILE, AND FOR FLAT ROOFS
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX.8412