Plan Review Notes
Plan Review Notes For Permit 01010655
Permit Number 01010655
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-23 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
  
  
  
  
  
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 4) PLEASE CORRELATE OCP WITH WIRE SIZES
 ON PANEL SCHEDULE(S). ART 240
  
 5) PLEASE CORRELATE OCP WITH WIRE SIZES
 ON PANEL SCHEDULE(S). ART 240
  
 6) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 7) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 8)PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 9)NOTE: PLEASE NOTE THAT ON SHEET A-8
 YOU SHOW METER WITH NO MAIN DISCONNECT
 AND ON RISER DIAGRAM YOU SHOW MAIN DISC-
 ONNECT NEXT TO METER. PLEASE SHOW ON A-8
 IF THIS IS THE CASE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATAION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372