| 2001-01-23 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRNET PER 110-9. |
| | |
| | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | |
| | 4) PLEASE CORRELATE OCP WITH WIRE SIZES |
| | ON PANEL SCHEDULE(S). ART 240 |
| | |
| | 5) PLEASE CORRELATE OCP WITH WIRE SIZES |
| | ON PANEL SCHEDULE(S). ART 240 |
| | |
| | 6) PLEASE CLARIFY EQUIPMENT GROUNDING |
| | METHOD BETWEEN FIRST MEANS OF DISCONNECT |
| | AND PANEL(S). EQUIPMENT GROUNDING |
| | CONDUCTORS ARE TO BE SIZED BY 250-122. |
| | |
| | 7) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | |
| | 8)PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. |
| | |
| | 9)NOTE: PLEASE NOTE THAT ON SHEET A-8 |
| | YOU SHOW METER WITH NO MAIN DISCONNECT |
| | AND ON RISER DIAGRAM YOU SHOW MAIN DISC- |
| | ONNECT NEXT TO METER. PLEASE SHOW ON A-8 |
| | IF THIS IS THE CASE. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATAION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |