| Plan Review Notes For Permit 01010653 |
| Permit Number |
01010653 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-25 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRNET PER 110-9. | | | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 3) PLEASE NOTE MISSING OUTLET(S) REQ`D | | | BY 210-52E OF THE NEC. | | | | | | 4) PLEASE CLARIFY EQUIPMENT GROUNDING | | | METHOD BETWEEN FIRST MEANS OF DISCONNECT | | | AND PANEL(S). EQUIPMENT GROUNDING | | | CONDUCTORS ARE TO BE SIZED BY 250-122. | | | | | | 5)NOTE: PLEASE NOTE THE PLANS SHOW TWO | | | PANELS IN GARAGE. RISER DIAGRAM SHOWS | | | ONLY ONE PANEL? PLEASE CLARIFY. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS P | | | LEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|