| Plan Review Notes For Permit 01010575 |
| Permit Number |
01010575 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-06 00:00:00 | ****************** UNSAT *************** | | | | | | 1) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 2)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | KITCHEN COUNTERSPACE. PER 210-52-C-1 | | | | | | 3)NOTE: NO ELECTRICAL SUBMITTED FOR | | | SERVICE ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION AND | | | SUBMIT MORE INFORMATION FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|