Plan Review Notes
Plan Review Notes For Permit 01010549
Permit Number 01010549
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-23 00:00:00DENIED;
  
 1.MOP SINK IS IN THE ACCESSIBLE ROUTE
 OF THE BATHROOM 97 FACBC 4.3.
  
 2.WATER HEATER MUST BE READILY
 ACCESSIBLE 94 SPC 501.7. INSTALL W/H
 ON FLOOR OR INSTALL A FIXED SHIPS
 LADDER.
  
 3.3" FLOOR DRAIN WITH TRAP PRIMER
 REQUIRED IN RESTROOM. SPC 409.4.1.1.
  
 4.BATHROOM CANNOT OPEN DIRECTLY INTO
 A ROOM USED FOR THE PREPARATION OF
 FOOD FOR THE PREPARATION OF FOOD FOR
 SERVICE TO THE PUBLIC SPC 404.2.
  
 5.(AIR CHAMBER DETAIL) AIR CHAMBERS
 SHALL COMPLY WITH SPC 607.8.1. MUST
 BE ENGINEERED OR CALCULATED AND COMPLY
 WITH 607.8.3. THEY MUST BE ACCESSIBLE.
  
 6.SEPORATE GREASY WASTE LINE REQUIRED
 FOR MOP SINK AND THE TWO FLOOR SINKS
 AND RUN TO EXISTING GREASE TRAP.
  
 7.A-3 WATER HEATER DETAIL SHOWS 50 GAL.
 LOW BOY. WATER RISER SHOWS 20 GAL.W/H.
 WHAT SIZE IS WATER HEATER.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377