Plan Review Notes
Plan Review Notes For Permit 01010543
Permit Number 01010543
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-30 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 4) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372